Chapter 4 Setup Menus

25

Table 4-3 Analog Output Setup Options

Code

Option

Description

OutP Output parameter

The output parameter for the analog output channel

Lo

Zero scale (0/4 mA)

The reading of the parameter corresponding to a zero-
scale current output

Hi

Full scale (1/20 mA)

The reading of the parameter corresponding to a full-scale
current output

Table 4-4 Analog Output Parameters

Code

Parameter

Unit

Scale

nonE Output

disabled

0

Real-time Measurements
r. U 1

Voltage L1/L12

V/kV

0 to Vmax

r. U 2

Voltage L2/L23

V/kV

0 to Vmax

r. U 3

Voltage L3/L31

V/kV

0 to Vmax

r. C1

Current L1

A

0 to Imax

r. C2

Current L2

A

0 to Imax

r. C3

Current L3

A

0 to Imax

r. P

Total kW

kW/MW

-Pmax to Pmax

r. q

Total kvar

kvar/Mvar

-Pmax to Pmax

r. S

Total kVA

kVA/MVA

0 to Pmax

r. PF

Total PF

-0.000 to 0.000

r. PF.LG

Total PF lag

0 to 1.000

r. PF.Ld

Total PF lead

0 to 1.000

r. Fr

Frequency

Hz

0 to 100.00

Average Measurements
A. U 1

Voltage L1/L12

V/kV

0 to Vmax

A. U 2

Voltage L2/L23

V/kV

0 to Vmax

A. U 3

Voltage L3/L31

V/kV

0 to Vmax

A. C1

Current L1

A

0 to Imax

A. C2

Current L2

A

0 to Imax

A. C3

Current L3

A

0 to Imax

A. P

Total kW

kW/MW

-Pmax to Pmax

A. q

Total kvar

kvar/Mvar

-Pmax to Pmax

A. S

Total kVA

kVA/MVA

0 to Pmax

A. PF

Total PF

-0.000 to 0.000

A. PF.LG

Total PF lag

0 to 1.000

A. PF.Ld

Total PF lead

0 to 1.000

A. neU.C

Neutral current

A

0 to Imax

A. Fr

Frequency

Hz

0 to 100.00

Present Demands
Accd.P

Accumulated kW demand

kW/MW

0 to Pmax

Accd.S

Accumulated kVA demand

kVA/MVA

0 to Pmax

Imax (20% over-range) = 1.2

× CT primary current [A]

Direct wiring (PT Ratio = 1):

Vmax (690 V input option) = 828.0 V
Vmax (120 V input option) = 144.0 V
Pmax = (Imax

× Vmax × 3) [kW x 0.001] @ wiring modes 4Ln3, 3Ln3

Pmax = (Imax

× Vmax × 2) [kW x 0.001] @ wiring modes 4LL3, 3OP2, 3dir2, 3OP3, 3LL3