4.9 User Selectable Options Menu

This menu allows you to change options which relate to the instrument features
and functionality. Table 4-10 lists all available options with their code names and
applicable ranges.

To select an option:

Press to activate the middle window, and then use the

up/down arrow keys to scroll to the desired option.

To change the selected option:

Press to activate the lower window.
Use the up/down arrow keys to set the desired value.
Press to store your new setting or to leave the

previous setting unchanged.

To quit the display setup menu:

From the middle window, press or .


Table 4-10 User Selectable Options (

∗ default setting)

Code

Parameter

Options

Description

P.cAL

Power calculation
mode

rEAc*
nAct

Using reactive power
Using non-active power

roLL

Energy roll value

10.E4
10.E5
10.E6
10.E7
10.E8
*

10,000 kWh
100,000 kWh
1,000,000 kWh
10,000,000 kWh
100,000,000 kWh

Ph.En

Phase energy
measurements

diS*, En

Enables/disables measurements of
energies per phase

Power calculation mode (P.cAL):

Mode 1: Reactive power calculation (rEAc)

Active power P and reactive power Q are measured directly and apparent power
S =

√ P

2

+ Q

2

Mode 2: Non-active power calculation (nAct)

Active power is measured directly, apparent power S = V

× I (where V, I - rms

voltage and currents) and non-active power N =

√ S

2

-

P

2

Mode 1 is recommended for electrical networks with low harmonic distortion (voltage
THD

< 5%, current THD < 10%); Mode 2 is recommended for all other cases.

SELECT

SELECT

OPtS

rEAc

P.cAL

ENTER

ESC

ESC

ENTER

SELECT

CHG

OPtS

ENTER

ENTER