Chapter 4 Setup Menus

29

Table 4-6 Setpoint Setup Options (middle window)

Code

Option

Description

triG

Trigger parameter

The measurement parameter or signal to be monitored
by the setpoint.

On

Operate limit

The threshold at which the setpoint becomes operative.

OFF

Release limit

The threshold at which the setpoint is released (becomes
inoperative).

On d

Operate delay

The time delay (0.1 second resolution) before operation
when the operate condition is fulfilled.

OFF d

Release delay

The time delay (0.1 second resolution) before release
when the release condition is fulfilled.

Act

Setpoint action

The action performed when the setpoint is operative.

Table 4-7 Setpoint Triggers (lower window, when middle window is triG)

Code

Parameter

Unit

Range

nonE

Setpoint disabled

Status Input
St.On

Status input ON

St.OFF

Status input OFF

Phase Reversal
POS.ro.

Positive phase rotation reversal

NEG.ro.

Negative phase rotation reversal

Real-time Values on any Phase
r. Hi. U

High voltage

V

0 to Vmax

r. Lo. U

Low voltage

V

0 to Vmax

r. Hi. C

High current

A

0 to Imax

r. Lo. C

Low current

A

0 to Imax

r. thd.U

High voltage THD

%

0 to 999.9

r. thd.C

High current THD

%

0 to 999.9

r. HFc.C

High K-factor

%

1.0 to 999.9

r. tdd.C

High current TDD

%

0 to 100.0

Real-time Auxiliary Measurements
r. Hi.Fr

High frequency

Hz

0 to 100.00

r. Lo.Fr

Low frequency

Hz

0 to 100.00

Average Values per Phase
A. Hi.C1

High current L1

A

0 to Imax

A. Hi.C2

High current L2

A

0 to Imax

A. Hi.C3

High current L3

A

0 to Imax

A. Lo.C1

Low current L1

A

0 to Imax

A. Lo.C2

Low current L2

A

0 to Imax

A. Lo.C3

Low current L3

A

0 to Imax

Average Values on any Phase
A. Hi. U

High voltage

V

0 to Vmax

A. Lo. U

Low voltage

V

0 to Vmax

A. Hi. C

High current

A

0 to Imax

A. Lo. C

Low current

A

0 to Imax

Average Total Values

A. Hi.P.i

High total kW import (positive)

kW

0 to Pmax

A. Hi.P.E

High total kW export (negative)

kW

0 to Pmax

A. Hi.q.i

High total kvar import (positive)

kvar

0 to Pmax

A. Hi.q.E

High total kvar export (negative)

kvar

0 to Pmax

A. Hi. S

High total kVA

kVA

0 to Pmax

A. PF.LG

Low total PF Lag

0 to 1.000