4.4 Analog Output Setup Menu

[This section is relevant to instruments ordered with this option.]

This menu allows you to set up an output value and its zero and full scales for
the internal analog output. Table 4-3 explains the analog output setup options,
and Table 4-4 lists all measurement parameters that can be directed to analog
output.

Output parameter




Zero-scale output

Full-scale output

To view the setup options for the analog output:

Press to activate the middle window.
Use the up/down arrow keys to scroll to the desired option. The value

associated with this option is displayed in the lower window.

To change the setup options for the selected channel:

Press to activate the lower window.
Use the up/down arrow keys to scroll to the desired value.
Press to store the selected value, or press to leave the value

unchanged.

Press again to store the setup for the channel.

To quit the setup without changes:

From the middle or lower window, press .

To quit the menu:

From the upper window, press or .

NOTES
1.

Except for the signed power factor, the output scale is linear within the value range.

The scale range will be inverted if the full scale specified is less than the zero scale.

2.

The output scale for the signed power factor is symmetrical with regard to

±1.000 and

is linear from -0 to -1.000, and from 1.000 to +0 (note that -1.000

≡ +1.000). Negative

power factor is output as [-1.000 minus measured value], and non-negative power
factor is output as [+1.000 minus measured value]. To define the entire range for
power factor from -0 to +0, the scales would be specified as -0.000/0.000.

3.

Each time you select the output parameter for the analog channel, its zero and full

scales are set by default to the lower and upper parameter limits, respectively.

SELECT

SELECT

ENTER

ESC

ENTER

ESC

ESC

ENTER

Aout

828

Hi

Aout

rt U1

Outp

Aout

0

Lo

SELECT

CHG

Aout

ENTER

ENTER