background image

English-19

Refer to the PowerFlex 40P User Manual supplied with the drive for
complete listing of parameters.

To clear a fault, press the Stop key, cycle power or set A100 [Fault Clear] to 1 or
2.

Enhanced Program Group Parameters

= Stop drive before changing this parameter.

No.

Parameter

Min/Max

Display/Options

Default

E216

[Motor Fdbk Type]

0/5

0 = “None”
1 = “Pulse Train”
2 = “Single Chain”
3 = “Single Check”
4 = “Quadrature”
5 = “Quad Check”

0

Selects the encoder type.

E217

[Motor NP Poles]

2/40

1

4

Defines the number of poles in the motor.

E218

[Encoder PPR]

1/20000

1

1024

Specifies the encoder pulses per revolution when
an encoder is used. For additional information refer
to Appendix F of the PowerFlex 40P User Manual.

Program Group Parameters

Advanced Display Group Parameters

No.

Parameter

Min/Max

Display/Options

d301 [Drive Status 2]

0/1

1

d302 [Fibers Status]

0/1

1

d303 [Slip Hz Meter]

0.0/25.0 Hz

0.1 Hz

d304 [Speed Feedback]

0/64000 RPM

1 RPM

d305 [Speed Feedback F]

0.0/0.9

0.1

d306 [Encoder Speed]

0/64000

1

d307 [Encoder Speed F]

0.0/0.9

0.1

d308 [Units Traveled H]

0/64000

1

d309 [Units Traveled L]

0.00/0.99

0.01

d310 [Fault 4 Code]

0/122

1

d311 [Fault 5 Code]

0/122

1

d312 [Fault 6 Code]

0/122

1

d313 [Fault 7 Code]

0/122

1

d314 [Fault 8 Code]

0/122

1

d315 [Fault 9 Code]

0/122

1

d316 [Fault 10Code]

0/122

4

Fault Codes

No.

Fault

Description

F2

Auxiliary Input

(1)

Check remote wiring.
Verify communications programming for intentional fault.

F3

Power Loss

Monitor the incoming AC line for low voltage or line power interruption.
Check input fuses.

F4

UnderVoltage

(1)

Monitor the incoming AC line for low voltage or line power interruption.

F5

OverVoltage

(1)

Monitor the AC line for high line voltage or transient conditions. Bus overvoltage can also be
caused by motor regeneration. Extend the decel time or install dynamic brake option.