Signal and Control Wire Types

Recommended Control Wire for Digital I/O

I/O Terminal Block Specifications

Refer to the PowerFlex 40P User Manual for recommendations on
maximum power and control cable length.

I/O Wiring Recommendations

Signal Type/
Where Used

Belden Wire Type(s)

(1)

(or equivalent)

(1)

Stranded or solid wire.

Description

Min. Insulation
Rating

Analog I/O & PTC

8760/9460

0.750 mm

2

(18AWG), twisted

pair, 100% shield with drain

(3)

(3)

If the wires are short and contained within a cabinet which has no sensitive circuits,
the use of shielded wire may not be necessary, but is always recommended.

300V,
75-90

°

C

(167-194

°

F)

Remote Pot

8770

0.750 mm

2

(18AWG), 3

cond., shielded

Encoder/Pulse I/O

89730

(2)

(2)

9728 or 9730 are equivalent and may be used but may not fit in the drive wire channel.

0.196 mm

2

(24AWG),

individually shielded pairs

Type

Wire Type(s)

Description

Minimum
Insulation Rating

Unshielded Per US NEC or applicable

national or local code

300V,
60 degrees C
(140 degrees F)

Shielded

Multi-conductor shielded
cable such as Belden
8770(or equiv.)

0.750 mm

2

(18AWG), 3

conductor, shielded.

Frame

Maximum Wire Size

(1)

(1)

Maximum/minimum sizes that the terminal block will accept - these are not
recommendations.

Minimum Wire Size

(1)

Torque

B & C

1.3 mm

2

(16 AWG)

0.2 mm

2

(24 AWG)

0.5-0.8 N-m (4.4-7 lb.-in.)