Mounting considerations, Minimum mounting clearances, Ambient operating temperatures – Rockwell Automation 25D PowerFlex 40P Quick Start - FRN 1.xx - 3.xx User Manual

Page 2: See page 21 for moun ting dimensions

Advertising
background image

English-2

Mount the drive upright on a flat, vertical and level surface.

Protect the cooling fan by avoiding dust or metallic particles.

Do not expose to a corrosive atmosphere.

Protect from moisture and direct sunlight.

Minimum Mounting Clearances

See page 21 for mounting dimensions.

Ambient Operating Temperatures

Mounting Considerations

Frame

Screw Size

Screw Torque

DIN Rail

B

M4 (#8-32)

1.56-1.96 N-m (14-17 lb.-in.)

35 mm

C

M5 (#10-24)

2.45-2.94 N-m (22-26 lb.-in.)

Ambient Temperature

Enclosure Rating

Minimum Mounting
Clearances

Minimum

Maximum

-10°C (14°F)

40°C (104°F)

IP 20/Open Type

Use Mounting Option A

IP 30/NEMA 1/UL Type 1

(1)

(1)

Rating requires installation of the PowerFlex 40P IP 30/NEMA 1/UL Type 1 option kit.

Use Mounting Option B

50°C (122°F) IP 20/Open Type

Use Mounting Option B

25 mm

(1.0 in.)

120 mm

(4.7 in.)

120 mm

(4.7 in.)

120 mm

(4.7 in.)

120 mm

(4.7 in.)

RUN
REV

FAULT

RUN
REV

FAULT

RUN
REV

FAULT

RUN
REV

FAULT

Mounting Option A

No clearance required

between drives.

Mounting Option B

Closest object that

may restrict air flow

through the drive heat

sink and chassis

Advertising