Power Terminal Block

Control Outputs Relay:

Quantity:

(1) Programmable Form C

Specification

Resistive Rating:
Inductive Rating:

3.0A at 30V DC, 3.0A at 125V, 3.0A at 240V AC
0.5A at 30V DC, 0.5A at 125V, 0.5A at 240V AC

Opto:

Quantity:

(2) Programmable

Specification:

30V DC, 50mA Non-inductive

Analog:

Quantity:

(1) Non-Isolated 0-10V or 4-20mA

Specification

Resolution:
0 to 10V DC Analog:
4-20mA Analog:

10-bit
1k ohm minimum
525 ohm maximum

Category

Specification

Power Wiring

Power Wire Rating

Recommended Copper Wire

Unshielded 600V, 75°C (167°F) THHN/THWN

15 Mils insulated, dry location

Shielded 600V, 75°C or 90°C (167°F or 194°F) RHH/
RHW-2

Anixter OLF-7xxxxx,
Belden 29501-29507 or
equivalent

Shielded Tray rated 600V, 75°C or 90°C (167°F or
194°F) RHH/RHW-2

Anixter 7V-7xxxx-3G
Shawflex 2ACD/3ACD or
equivalent

Terminal

(1)

Description

R/L1, S/L2

1-Phase Input

(2)

R/L1, S/L2, T/L3 3-Phase Input

U/T1

To Motor U/T1

=

Switch any two motor
leads to change
forward direction.

V/T2

To Motor V/T2

W/T3

To Motor W/T3

P2, P1

DC Bus Inductor Connection (C Frame drives only.)

The C Frame drive is shipped with a jumper between
Terminals P2 and P1. Remove this jumper only when a DC
Bus Inductor will be connected. Drive will not power up
without a jumper or inductor connected.

DC+, DC-

DC Bus Connection

BR+, BR-

Dynamic Brake Resistor Connection

Safety Ground - PE

(1)

Important: Terminal screws may become loose during shipment. Ensure that all
terminal screws are tightened to the recommended torque before applying power to
the drive.

(2)

Single-phase operation requires a 65% derate of drive rated current.

V/T2

T/L3

S/L2

R/L1

U/T1

W/T3

BR+

BR-

DC- DC+

V/T2

T/L3

S/L2

R/L1

U/T1

W/T3

P2

P1

BR+

BR-

DC- DC+

B Frame

C Frame