Typical grounding, Disconnecting movs, Important: tighten screw after jumper removal – Rockwell Automation 25D PowerFlex 40P Quick Start - FRN 1.xx - 3.xx User Manual

Page 3

Advertising
background image

English-3

To prevent drive damage, the MOVs connected to ground shall be
disconnected if the drive is installed on an ungrounded distribution
system where the line-to-ground voltages on any phase could exceed
125% of the nominal line-to-line voltage. To disconnect these devices,
remove the jumper shown in the figures below.

1. Turn the screw counterclockwise to loosen.

2. Pull the jumper completely out of the drive chassis.

3. Tighten the screw to keep it in place.

Jumper Location

Phase to Ground MOV Removal

Important: Tighten screw after jumper removal.

Typical Grounding

SHLD

U/T1

V/T2

W/T3

R/L1

S/L2

T/L3

RUN
REV

FAULT

Disconnecting MOVs

R/L1
S/L2
T/L3

1

2

3

4

Three-Phase

AC Input

Jumper

Advertising