Drive ratings – Rockwell Automation 25D PowerFlex 40P Quick Start - FRN 1.xx - 3.xx User Manual

Page 4

Advertising
background image

English-4

Refer to the PowerFlex 40P User Manual for details on how to comply
with the Low Voltage (LV) and Electromagnetic Compatibility (EMC)
Directives.

Drive Ratings

CE Conformity

Specifications, Fuses and Circuit Breakers

Catalog
Number

(1)

Output Ratings

Input Ratings

Branch Circuit Protection

kW (HP)

Amps

Voltage

Range

kVA

Amps

Fuses

140M Motor
Protectors

(2)

(3)

Contactors

Min. Enclosure

Volume

(4)

(in.

3

)

200 - 240V AC (±10%) – 3-Phase Input, 0 - 230V 3-Phase Output

22D-B2P3

0.4 (0.5)

2.3

180-264

1.15

2.5

6

140M-C2E-B40

100-C07

1655

22D-B5P0

0.75 (1.0)

5.0

180-264

2.45

5.7

10

140M-C2E-C10

100-C09

1655

22D-B8P0

1.5 (2.0)

8.0

180-264

4.0

9.5

15

140M-C2E-C16

100-C12

1655

22D-B012

2.2 (3.0)

12.0

180-264

5.5

15.5

25

140M-C2E-C16

100-C23

1655

22D-B017

3.7 (5.0)

17.5

180-264

8.6

21.0

30

140M-F8E-C25

100-C23

1655

22D-B024

5.5 (7.5)

24.0

180-264

11.8

26.1

40

140M-F8E-C32

100-C37

2069

22D-B033

7.5 (10.0)

33.0

180-264

16.3

34.6

60

140M-G8E-C45 100-C60

2069

380 - 480V AC (±10%) – 3-Phase

Input, 0 - 460V 3-Phase Output

22D-D1P4

0.4 (0.5)

1.4

342-528

1.4

1.8

3

140M-C2E-B25

100-C07

1655

22D-D2P3

0.75 (1.0)

2.3

342-528

2.3

3.2

6

140M-C2E-B40

100-C07

1655

22D-D4P0

1.5 (2.0)

4.0

342-528

4.0

5.7

10

140M-C2E-B63

100-C09

1655

22D-D6P0

2.2 (3.0)

6.0

342-528

5.9

7.5

15

140M-C2E-C10

100-C09

1655

22D-D010

4.0 (5.0)

10.5

342-528

10.3

13.0

20

140M-C2E-C16

100-C23

1655

22D-D012

5.5 (7.5)

12.0

342-528

11.8

14.2

25

140M-D8E-C20

100-C23

2069

22D-D017

7.5 (10.0)

17.0

342-528

16.8

18.4

30

140M-D8E-C20

100-C23

2069

22D-D024

11.0 (15.0)

24.0

342-528

23.4

26.0

50

140M-F8E-C32

100-C43

2069

460 - 600V AC (±10%) – 3-Phase

Input, 0 - 575V 3-Phase Output

22D-E1P7

0.75 (1.0)

1.7

414-660

2.1

2.3

6

140M-C2E-B25

100-C09

1655

22D-E3P0

1.5 (2.0)

3.0

414-660

3.65

3.8

6

140M-C2E-B40

100-C09

1655

22D-E4P2

2.2 (3.0)

4.2

414-660

5.2

5.3

10

140M-D8E-B63

100-C09

1655

22D-E6P6

4.0 (5.0)

6.6

414-660

8.1

8.3

15

140M-D8E-C10

100-C09

1655

22D-E9P9

5.5 (7.5)

9.9

414-660

12.1

11.2

20

140M-D8E-C16

100-C16

2069

22D-E012

7.5 (10.0)

12.2

414-660

14.9

13.7

25

140M-D8E-C16

100-C23

2069

22D-E019

11.0 (15.0)

19.0

414-660

23.1

24.1

40

140M-F8E-C25

100-C30

2069

(1)

Ratings apply to all drive types; Panel Mount (N104), Flange Mount (F104), and Plate Drive
(H204).

(2)

The AIC ratings of the Bulletin 140M Motor Protector Circuit Breakers may vary. See

Bulletin 140M

Motor Protection Circuit Breakers Application Ratings

.

(3)

Manual Self-Protected (Type E) Combination Motor Controller, UL listed for 208 Wye or Delta, 240
Wye or Delta, 480Y/277 or 600Y/347. Not UL listed for use on 480V or 600V Delta/Delta, corner
ground, or high-resistance ground systems.

(4)

When using a Manual Self-Protected (Type E) Combination Motor Controller, the drive must be
installed in a ventilated or non-ventilated enclosure with the minimum volume specified in this
column. Application specific thermal considerations may require a larger enclosure.