12

Rockwell Automation Publication 23B-IN001K-EN-P - September 2013

Chapter 1

PowerFlex 40 Standard Configured Drive Standard Features and Options

Power Disconnect Options

Drive Motor Circuit Protector (Position 16+, Code P3)

The Drive Motor Circuit Protector option is factory installed and provides a
manual means of disconnecting input power to the drive. The Allen-Bradley
bulletin 140M switch is designed to meet short circuit requirements for branch
circuit protection. The rotary style handle is padlockable in On or Off position.
See

Table 1

for the short circuit withstand rating of this option. Over load

protection is supplied by the drive—not the motor circuit protector. Incoming
customer supplied power cables terminate at terminals R, S, T (L1, L2, L3)
located on the

bottom of the device.

Component Specifications

Drive Motor Circuit Protector (Position 16+, Code P3T)

The Drive Motor Circuit Protector option is factory installed and provides a
manual means of disconnecting input power to the drive. The Allen-Bradley
bulletin 140M switch is designed to meet short circuit requirements for branch
circuit protection. The rotary style handle is padlockable in On or Off position.
See

Table 1

for the short circuit withstand rating of this option. Over load

protection is supplied by the drive—not the motor circuit protector. Incoming
customer supplied power cables terminate at terminals R, S, T (L1, L2, L3)
located on the

top of the device.

Component Specifications

Table 1 - Drive Option P3 and P3T Short Circuit Withstand Ratings

Switch

Allen-Bradley Bulletin 140M, 480V, see

Table 1

for short circuit withstand rating

To be used only with grounded wye neutral AC distribution systems
3-pole, Rod operated
UL listed, CE Approved, CSA Certified

Handle

Rotary style handle through the door, Door interlocked
Padlockable in On or Off position, Defeatable in the On position
IP66 (Type 3R, 3, 12, 4, 4X)

Switch

Allen-Bradley Bulletin 140M, 480V, see

Table 1

short circuit withstand rating

To be used only with grounded wye neutral AC distribution systems
3-pole, Rod operated
UL listed, CE Approved, CSA Certified

Handle

Rotary style handle through the door, Door interlocked
Padlockable in On or Off position, Defeatable in the On position
IP66 (Type 3R, 3, 12, 4, 4X)

Drive Rating

Option P3 / P3T Short Circuit
Withstand Rating

0.5, 1, 2, 3, 7.5, 10, and 15 HP

65 kA

5 HP

30 kA