Appendix a, Specifications, Specifications tables – Rockwell Automation 22B PowerFlex 40 Configured AC Drives User Manual

Page 55: Appendix

Advertising
background image

Rockwell Automation Publication 23B-IN001K-EN-P - September 2013

55

Appendix

A

Specifications

The following tables provide specifications for the PowerFlex 40 configured AC
drives.

Specifications Tables

Table 6 - Standard Configured Drive Products

Table 7 - Standard PowerFlex 40 Drives

Input/Output Ratings

Output Frequency: 0…400

Hz

(Programmable)

Efficiency: 97.5%

(Typical)

Approvals

Fuses and Power
Disconnecting Means

140M Motor Circuit Protector:

Provides branch circuit protection, see

Table 1 on page 12

for short circuit withstand rating, on grounded wye

neutral distribution systems only

194R Fused Disconnect:

Provides branch circuit protection, 200 kA short circuit withstand, Class J fuses

Protective Features

Over Voltage:

480V AC Input – Trip occurs at 810V DC bus voltage (equivalent to 575V AC incoming line)

Under Voltage:

480V AC Input – Trip occurs at 390V DC bus voltage (equivalent to 275V AC incoming line)

Environment

Ambient Operating Temperature, NEMA 4/12, 4X (IP66): –10 to 40 degrees C (14 to 104 degrees F)

(1)

Cooling Method:

Fan (All drive ratings)

Control

Carrier Frequency:

2…4 kHz. Drive rating and heat calculations are based on 4 kHz.

(1) The design of the PowerFlex 40 Standard Configured Drive NEMA 4/12 and 4X packages support indoor and outdoor applications that are not in direct sunlight. When optional Door Mounted HIM is

supplied, enclosure is rated for indoor use only.

UL

®

LIS

TED 966X

IND C

O NT EQ

UL508C

UL

®

LIS

TED 966X

IND C

O NT EQ

C

CSA C 22.2 No. 14

Digital Control Inputs
(Input Current = 6 mA)

SRC (Source) Mode:

18…24 Volts = ON; 0…6 Volts = OFF

SNK (Sink) Mode:

0…6 Volts = ON; 18…24 Volts = OFF

Analog Control Inputs

4-20mA Analog:

250 ohm input impedance

0-10V DC Analog:

100k ohm input impedance

External Pot:

1…10k ohms, 2 Watt minimum

Control Output

Programmable Output (form C relay)
Resistive Rating:

3.0A at 30V DC, 3.0A at 125V AC, 3.0A at 240V AC

Inductive Rating:

0.5A at 30V DC, 0.5A at 125V AC, 0.5A at 240V AC

Opto Outputs
30V DC, 50 mA
Non-inductive

Analog Output (10-bit)
0-10V, 1k ohm Min.

Fuses and Circuit Breakers

Recommended Fuse Type:

UL Class J, CC, T or Type BS88; 600V (550V) or equivalent.

Recommended Circuit Breakers: HMCP circuit breaker or equivalent.

Protective Features

Motor Protection:

I

2

t overload protection – 150% for 60 Secs, 200% for 3 Secs (Provides Class 10 protection)

Overcurrent:

200% hardware limit, 300% instantaneous fault

Control Ride Through:

Minimum ride through is 0.5 Secs - typical value 2 Secs

Faultless Power Ride Through: 100

milliseconds