Main Fuses (F1-F3)

Input line branch circuit protection fuses must be used to protect the input
power lines. If input fuses are not provided with your drive, recommended fuse
values are shown in

Table 2

. The input fuse ratings listed in

Table 2

are applicable

for one drive per branch circuit. No other load may be applied to that fused
circuit.

The recommended fuse type for all PowerFlex 40 Standard Configured Drives is
UL Class J.

Table 2 - Branch Fusing

ATTENTION: Most codes require that upstream branch circuit protection be
provided to protect input power wiring. Install the fuses recommended in

Table

2

. Do not exceed the fuse ratings. Failure to observe this precaution could result

in damage to, or destruction of, the equipment.

Voltage Rating

Drive Rating HP

Fuse Rating Amps

480V AC

0.5

3

1.0

6

2.0

10

3.0

15

5.0

20

7.5

25

10

30

15

50