Input power wiring – Rockwell Automation 22B PowerFlex 40 Configured AC Drives User Manual

Page 15

Advertising
background image

Rockwell Automation Publication 23B-IN001K-EN-P - September 2013

15

PowerFlex 40 Standard Configured Drive Standard Features and Options

Chapter 1

Input Power Wiring

Refer to the PowerFlex 40 User Manual for additional detailed information about
input power wiring recommendations and selection.

To connect AC input power to the drive package:

1. Select the proper wire size according to NEC and all applicable local codes

and standards. Note that you must punch openings in the Option Cabinet
of the desired conduit size, following NEC and all applicable local codes
and standards. Power terminal block specifications are listed in

Table 3

.

2. Connect the three-phase AC input power leads (three-wire VAC) to the

appropriate terminals. Connect the AC input power leads to terminals
L1, L2, L3 on the fused disconnect switch or motor circuit protector.

Note: Drive Input Fused Disconnect Switch (-P6) and Drive Motor
Circuit Protector (-P3) options are bottom fed. Drive Input Fused
Disconnect Switch (-P6T) and Drive Motor Circuit Protector (-P3T)
options are top fed.

3. Tighten the AC input terminal power terminals to the proper torque

according to drive type as shown in

Table 3

.

Table 3 - Component Current Ratings and Wire Sizing

ATTENTION: Protect the contents of the options cabinet from metal chips and
other debris while drilling the conduit openings. Failure to observe this
precaution could result in damage to, or destruction of, the equipment.

ATTENTION: Do not route signal and control wiring with power wiring in the
same conduit. This can cause interference with drive operation. Failure to
observe this precaution could result in damage to, or destruction of, the
equipment.

PowerFlex 40 SPD Drive Rating - 480V

HP

Continuous Current
Rating
Amps

Factory Power Wire
Size

(1)(2)

(1) Wire is Black Hypalon.
(2) Maximum/minimum sizes that the terminal block will accept - these are not recommendations.

Customer Terminal
Wire Size

Operating Torque

0.5…3

30

2.5 mm

2

(14 AWG)

2.5…8.4 mm

2

(14…8 AWG)

1.6 N•m
(14 lb•in)

5…7.5

30

3.5 mm

2

(12 AWG)

2.5…8.4 mm

2

(14…8 AWG)

1.6 N•m
(14 lb•in)

10…15

60

4.0 mm

2

(10 AWG)

2.5…16.0 mm

2

(14…4 AWG)

2.8 N•m
(25 lb•in)