22

Rockwell Automation Publication 23B-IN001K-EN-P - September 2013

Chapter 1

PowerFlex 40 Standard Configured Drive Standard Features and Options

Spring Return Hand-Off-Auto Selector Switch (Code S22)

This 800F door mounted operator device is factory installed and provides a
Hand/Off/Auto selector switch. The Hand position is equipped with a spring
return.

The Hand/Off/Auto selector switch will start the drive while held in Hand
mode and stop the drive in Off mode. The selector switch has a spring return
disallowing the operator to remain in Hand. In Auto mode the drive will be
stopped and started from remote contact closures. In all cases, the Stop input to
the drive must be present before the drive will start.

The Hand/Off/Auto selector switch also determines the source of the actual
drive speed reference. In Hand mode, speed source is parameter A072 [Preset
Freq 2]. In Auto mode, speed source is parameter A071 [Preset Freq 1].

If the door mounted speed potentiometer (Option S18) is supplied and it is
intended to be the speed reference in Hand mode, set parameter A052 [Digital
In2 Sel] to option 13 “10V In Ctrl.”

Spring Return HOA Selector Switch (Code S22)

Component Specifications

This option is not compatible with Codes R3, R5, S1, S4, S7, S20 or S21.

Speed Reference

Parameter Settings

Hand Mode

Auto Mode

P038 [Speed Reference]

A051 [Digital In1 Sel]

A052 [Digital In2 Sel]

Preset Speed

Preset Speed

4 “Preset Freq”

4 “Preset Freq”

4 “Preset Freq”

Analog Input (0-10V)

4 “Preset Freq”

13 “10V In Ctrl”

4 “Preset Freq”

Analog Input (4-20mA)

4 “Preset Freq”

14 “20mA In Ctrl”

4 “Preset Freq”

Communication Port

(1)

4 “Preset Freq”

6 “Comm Port”

4 “Preset Freq”

Speed Pot (Door)

Preset Speed

4 “Preset Freq”

4 “Preset Freq”

13 “10V In Ctrl”

Analog Input (4-20mA)

4 “Preset Freq”

14 “20mA In Ctrl”

13 “10V In Ctrl”

Communication Port

(1)

4 “Preset Freq”

6 “Comm Port”

13 “10V In Ctrl”

HIM (Door)

Preset Speed

4 “Preset Freq”

4 “Preset Freq”

6 “Comm Port”

Analog Input (0-10V)

4 “Preset Freq”

13 “10V In Ctrl”

6 “Comm Port”

Analog Input (4-20mA)

4 “Preset Freq”

14 “20mA In Ctrl”

6 “Comm Port”

(1) Communication port will have both logic and reference control.

Bulletin 800F Devices

IEC style, Internationally rated
Meet IP65/IP66 and NEMA/UL Type 4/4X/13
UL Listed, CSA Certified
10 amp contacts
Screw terminals, 0.3…3.5 mm

2

(22…12 AWG) maximum

Hand/Off/Auto Selector
Switch:

3 position, Hand (spring return), Off, Auto (maintained), 4 N.O. contacts

Legend Plate

30 x 50 mm, Black with white lettering

Wiring

0.8 mm

2

(18 AWG), Blue

Schematic

Figure 16 on page 43