Rockwell Automation 22B PowerFlex 40 Configured AC Drives User Manual

Page 56

Advertising
background image

56

Rockwell Automation Publication 23B-IN001K-EN-P - September 2013

Appendix A

Specifications

Dynamic Braking

Internal brake IGBT included with all ratings

Environment

Altitude:

1000 m (3300 ft) max. without derating

Storage Temperature:

–40 to 85 degrees C (–40 to 185 degrees F)

Atmosphere:

Important: Drive must not be installed in an area where the ambient atmosphere contains volatile or
corrosive gas, vapors or dust. If the drive is not going to be installed for a period of time, it must be stored in an
area where it will not be exposed to a corrosive atmosphere.

Relative Humidity:

0 to 95% non-condensing

Shock (operating):

15G peak for 11ms duration (±1.0ms)

Vibration (operating):

1G peak, 5 to 2000 Hz

Control

Frequency Accuracy
Digital Input:

Within ±0.05% of set output frequency.

Analog Input:

Within 0.5% of maximum output frequency.

Analog Output:

±2% of full scale, 10-bit resolution.

Speed Regulation - Open Loop with Slip Compensation:

±2% of base speed across a 40:1 speed range.
1% of base speed across a 60:1 speed range.

Stop Modes:

Multiple programmable stop modes including - Ramp, Coast, DC-Brake, Ramp-to-Hold and S Curve.

Accel/Decel:

Two independently programmable accel and decel times. Each time may be programmed from 0…600
seconds in 0.1 second increments.

Intermittent Overload:

150% Overload capability for up to 1 minute; 200% Overload capability for up to 3 seconds.

Electronic Motor Overload Protection: Class 10 motor overload protection according to NEC article 430 and motor over-temperature protection

according to NEC article 430.126 (A)(2). UL File E59272.

Advertising