Specifications – Rockwell Automation 56RF High Frequency 13.56 MHz RFID EtherNet/IP Interface Block User Manual
Page 15

High Frequency 13.56 MHz RFID EtherNet/IP Interface Block 15
Drawing Number
10000181820 Ver. 01 - November 2012
Specifications
EtherNet/IP Interface Block Input – 56RF-IN-IPS12, 56RF-IN-IPD22, and 56RF-IN-IPD22A
Attributes
Value
Number of inputs
2 – 56RF-IN-IPD22A
1 – all other modules
Input type
Sink, 24V DC
Voltage, off-state input, max.
5V DC
Voltage, on-state input, max.
30V DC
Voltage, on-state input, nom
24V DC
Voltage, on-state input, min.
11V DC
Current, off-state input, max.
1.5 mA @ 5V DC
Current, on-state input, max.
5 mA @ 30V DC
Voltage, sensor source, max.
30V DC
Voltage, sensor source, min.
10V DC
Input delay time
ON to OFF
OFF to ON
0…16000
µs
Isolation voltage
50V (continuous), Basic Insulation Type, Inputs and Sensor Power
to Network
No isolation between individual Inputs or between Network
channels Type tested at 707V DC for 60s
EtherNet/IP Interface Block Output – 56RF-IN-IPS12 and 56RF-IN-IPD22
Attributes
Value
Number of outputs
1
Output type
Source, 24V DC
Voltage drop, on-state output, max.
0.5V DC
Voltage off-peak blocking, min.
30V DC
Voltage, on-state output, max.
30V DC
Voltage, on-state output, min.
11V DC
Voltage, on-state output, nom
24V DC
Current on-state output, max.
0.5 A