Specifications – Rockwell Automation 56RF High Frequency 13.56 MHz RFID EtherNet/IP Interface Block User Manual

Page 15

Advertising
background image

High Frequency 13.56 MHz RFID EtherNet/IP Interface Block 15

Drawing Number

10000181820 Ver. 01 - November 2012

Specifications

EtherNet/IP Interface Block Input – 56RF-IN-IPS12, 56RF-IN-IPD22, and 56RF-IN-IPD22A

Attributes

Value

Number of inputs

2 – 56RF-IN-IPD22A
1 – all other modules

Input type

Sink, 24V DC

Voltage, off-state input, max.

5V DC

Voltage, on-state input, max.

30V DC

Voltage, on-state input, nom

24V DC

Voltage, on-state input, min.

11V DC

Current, off-state input, max.

1.5 mA @ 5V DC

Current, on-state input, max.

5 mA @ 30V DC

Voltage, sensor source, max.

30V DC

Voltage, sensor source, min.

10V DC

Input delay time

ON to OFF

OFF to ON

0…16000

µs

Isolation voltage

50V (continuous), Basic Insulation Type, Inputs and Sensor Power
to Network

No isolation between individual Inputs or between Network
channels Type tested at 707V DC for 60s

EtherNet/IP Interface Block Output – 56RF-IN-IPS12 and 56RF-IN-IPD22

Attributes

Value

Number of outputs

1

Output type

Source, 24V DC

Voltage drop, on-state output, max.

0.5V DC

Voltage off-peak blocking, min.

30V DC

Voltage, on-state output, max.

30V DC

Voltage, on-state output, min.

11V DC

Voltage, on-state output, nom

24V DC

Current on-state output, max.

0.5 A

Advertising