Getting Started Chapter 1

Quick Start

This section is provided to help experienced users quickly start using the option
module. If you are unsure how to complete a step, refer to the referenced chapter.

Step Action

See

1

Review the safety precautions for the option module.

Throughout this manual

2

Verify that the PowerFlex drive is properly installed.

PowerFlex 750-Series AC Drive
Installation Instructions,
publication

750-IN001

3

Install the option module.

a. Verify that the PowerFlex drive is not powered.

b. Set the source for the option module network

address with the IP Address Selection Jumper
(

Figure 1 on page 20

).

c. Insert the option module in drive Port 4, 5, or 6.

d. Use the captive screws to secure and ground the

option module to the drive.

e. Connect the option module to the network with a

Profinet Cable.

Important: When another module (I/O, encoder,
communication, and so forth) resides in the adjacent port
to the left of the 20-750-PNET2P option module—and the
lower mounting screw of that module is a larger T15 Torx
head screw, perform additional steps from 2a through 2c
on

page 21

.

Network Communication Option
Module Installation Instructions,
publication

750COM-IN002

, and

Chapter 2

,

Installing the Option Module

4

Apply power to the option module.

a. Verify that the option module is installed correctly.

The option module receives power from the drive.

b. Apply power to the drive.

The status indicators should be green. If they flash
red, there is a problem. See

Chapter 7

,

Troubleshooting

.

c. Configure and verify key drive parameters.

Chapter 2

,

Installing the Option Module

5

Configure the option module for your application.

Set option module parameters for the following functions
as required by your application:

Network Address
I/O configuration
Master-Slave hierarchy
Fault actions

Chapter 3

,

Configuring the Option Module

6

Configure the Profinet controller to communicate with the
option module.

Use a controller configuration tool to configure the
Profinet controller on the Profinet network to recognize
the option module and drive.

Chapter 4

,

Configuring the Profinet Master

7

Configure the I/O.

Use a controller configuration tool such as Profinet
Commander that enables you to control the option module
and connected drive using the I/O.

Chapter 5

,

Using the I/O