NET A Status Indicator

This red/green bicolor LED indicates the status of the Profinet network A
connection to the option module as shown in the table below.

NET B Status Indicator

This red/green bicolor LED indicates the status of the Profinet network B
connection to the option module as shown in the table below.

Status

Cause

Corrective Actions

Off

The option module is not using network A, or not
properly connected to network A.

Securely connect the option module to the drive and connect it to

network A using a Profinet cable.

Correctly connect the Profinet cable to the Port 1 Profinet connector.

Apply power to the drive.

Flashing Red

An error has occurred in network A configuration. Re-configure the Profinet module for network A.

Steady Red

An initialization error has occurred for network A
in ERTEC 200.

Cycle power to the drive.

Re-configure the Profinet controller.

Steady Green

The option module is properly connected and
communicating on network A.

No action required.

Status

Cause

Corrective Actions

Off

The option module is not using network B, or not
properly connected to network B.

Securely connect the option module to the drive and connect it to

network B using a Profinet cable.

Correctly connect the Profinet cable to the Port 2 Profinet connector.

Apply power to the drive.

Flashing Red

An error has occurred in network B configuration.

Re-configure the Profinet module for network B.

Steady Red

An initialization error has occurred for network B
in ERTEC 200.

Cycle power to the drive.

Re-configure the Profinet controller.

Steady Green

The option module is properly connected and
communicating on network B.

No action required.