Setting the ip address selection jumper, Setting the ip – Rockwell Automation 20-750-PNET2P Profinet Dual Port Option Module User Manual

Page 20

Advertising
background image

20

Rockwell Automation Publication 750COM-UM007A-EN-P - January 2013

Chapter 2 Installing the Option Module

Setting the IP Address
Selection Jumper

The IP Address Selection Jumper (

Figure 1

) determines the source of the IP

address for the option module. When the jumper is placed on Pins 2 and 3, either
the default network address is used or the network address may be configured
with option module parameters.

When the jumper is in this position, the setting for

Device Parameter 18 -

[DHCP]

does not have any effect.

The default network address is:

• IP Address 192.168.0.1
• Subnet Mask 255.255.255.0
• Gateway Address 192.168.0.1

If the jumper is on Pins 1 and 2—or there is no jumper—the network address is
configured by DCP/DHCP. If

Device Parameter 18 [DHCP] is set to ‘0’

(Disabled), the network address is configured by using a Profinet controller with
DCP capability. If

Device Parameter 18 [DHCP] is set to ‘1’ (Enabled), the

network address is configured from a DHCP server.

Figure 1 - Setting the IP Address Selection Jumper

1

3

2

Pins 1 and 2 (DCP-DHCP setting) to
use DCP capability or a DHCP server

Pins 2 and 3 (CONFIG setting) to use
option module parameters

Advertising