Configuring the Option Module Chapter 3

Restoring Option Module
Parameters to Factory
Defaults

As an alternate reset method, you can restore the option module parameters by
using a MEMORY folder menu item instead of using

Device Parameter 05 -

[Reset Module]

described in

Resetting the Option Module on page 38

. The

MEMORY folder method provides two ways to restore the option module

Device and Host parameters:

• ALL—restores ALL option module Device and Host parameters to their

factory default values.

• MOST—restores MOST option module Device and Host parameters—

except the following which are used for network setup:

Device Parameters 06 through 09 - [IP Addr Cfg 1-4]

Device Parameters 10 through 13 - [Subnet Cfg 1-4]

Device Parameters 14 through 17 - [Gateway Cfg 1-4]

Device Parameter 18 - [DHCP]

Follow these steps to restore option module

Device and Host parameters to their

factory default values.

1.

Access the Status screen, which is displayed on HIM powerup.

2.

Use the

or

key to scroll to the Port in which the option

module is installed.

3.

Press the

key to display its last-viewed folder.

4.

Use the

or

key to scroll to the MEMORY folder.

5.

Use the

or

key to select Set Defaults.

6.

Press the

(Enter) key to display the Set Defaults pop-up box.

7.

Press the

(Enter) key again to display the warning pop-up box to

reset

Device and Host parameters to their factory default values.

8.

Press the MOST

soft key to restore MOST Device and Host parameters to

factory defaults, or press the ALL

soft key to restore ALL parameters. Or

press the ESC

soft key to cancel.

IMPORTANT

When performing a Set Defaults, the drive may detect a conflict
and then not allow this function to occur. If this happens, first
resolve the conflict and then repeat this Set Defaults procedure.
Common reasons for a conflict include a drive running or a master
in Run mode.

00

Stopped

0.00 Hz

AUTO

Host Drive

240V

4.2A

Rev 3.002 Ser. A

ESC

REF

TEXT

F

PAR#