Chapter

3

Configuring the DeviceNet Encoder
DIP Switches

Chapter Objectives

Chapter 3 provides information that you need to configure the
encoder. In this chapter, you will read about the following:

Setting the node address.

Setting the transmission baud rate

Activating bus termination.

Diagnostic LED

The Preset function.

Setting up the 842D
DeviceNet Encoder

Specific features of the 842D must be configured by means of
hardware settings. (Remote setting of the DIP switches via a Node
Commissioning Tool is not supported at this time.) These features are
Node Address, Baud Rate and the DeviceNet bus termination. In
addition, the encoder can be set to a fixed position value (PRESET
function) by actuating a push-button. In order to execute this
function, the large PG plug on the rear of the encoder has to be
removed. Inside, three DIP switches and a micro push-button become
visible.

Figure 3.1

Encoder DIP Switches

(MAC-ID)

Preset Position
Button

Bus Termination

Baud Rate

Node Address