Chapter 5, Chapter objectives, Required equipment and software – Rockwell Automation 842D-60131331BXA DeviceNet Encoder User Manual User Manual

Page 27: Operating modes of the encoder, Explicit messaging, I/o messaging, Chapter

Advertising
background image

Chapter

5

Configuring a Scanner to
Communicate with the Encoder

Chapter Objectives

Chapter 5 provides instructions for configuring a PLC or SLC scanner
to communicate with the encoder.

Required Equipment and
Software

Before configuring the scanner, your PC must be:

Running RSNetWorx for DeviceNet. Refer to
http://www.software.rockwell.com for more information.

Connected to and communicating with the DeviceNet network
using a DeviceNet interface such as a 1784-PCD card or a
1770-KFD adapter.

Operating Modes of the
Encoder

There are two fundamentally different DeviceNet protocols:

Explicit messaging

I/O messaging

Explicit messaging

Explicit messaging is used for modifying the device configurations,
reading diagnostic values, program upload / download, etc.

Characteristics of explicit messaging:

Very flexible

Less efficient because each device must interpret and generate a
response

"Unbound" connections ("Hit and Run")

Contents of the data field:

Protocol information

Instructions for service to be performed

Internal address to which the service is to be applied

I/O messaging

I/O messaging is used for fast or time-critical data transfer. All of the
8 data bytes of the CAN telegram can be used for data transmission.
Characteristics of I/O messaging:

Less flexible

Advertising
This manual is related to the following products: