5-4

Configuring a Scanner to Communicate with the Encoder

Example DeviceNet Network

This section provides the steps that are needed to configure a simple
network that includes 1756-DNB/A scanner (Node 10) and an 842D
DeviceNet encoder (Node 03).

Setting Up the Scan List

For the scanner to communicate with a product, the scanner must be
configured and the product’s node number must be added to its scan
list.

1. Go online with RSNetWorx for DeviceNet. Refer to the “Going

Online” section in Chapter 4.

2. Select Network > Single Browse Path. The devices on the

network are displayed in the configuration view.

Figure 5.1

Configuration View (Graph)

3. Right-click the DeviceNet scanner (node 10 in Figure 5.1) and

select Properties. The Scanner Module dialog box appears.

Important: If your scanner is an unrecognized device, you must
create an EDS file for it and then configure it. Click Help or refer to
your scanner documentation if you need more information. Configure
the scanner using the General and Module tabs.

4. Click the Scanlist tab. A message box prompts you to upload.

5. Click Upload. Data is uploaded from the scanner, and then the

Scanlist page appears.