CGCM Unit Configuration Chapter 4

Related Parameters

EngineIdle
SoftStartTime

Power Tab

The Power tab is used to configure the unit’s parameters related to reverse power
and reverse reactive power protection. A higher setpoint value corresponds to
larger reverse power or VAR flow before a fault is declared.

Reverse kW Setpoint - Establishes the generator reverse kW setpoint in

percent of rated VA. The tag Rev_kW_Setpt stores this value in the
configuration table.

Reverse kW Fault Delay - Establishes the amount of time in seconds that

the reverse kW must be above the reverse kW setpoint before the CGCM
annunciates the fault. This parameter is stored in tag Rev_kW_TimeDly
in the configuration table.

Reverse kVAR Setpoint - Establishes the generator reverse kVar setpoint in

percent of rated VA. The tag Rev_kVAR_Setpt stores this value in the
configuration table.

Reverse kVAR Fault Delay - establishes the amount of time in seconds that

the reverse kVAR must be above the reverse kVAR setpoint before the
CGCM unit annunciates the fault. This parameter is stored in tag
Rev_kVAR_TimeDly

in the configuration table.

Related Parameters

GenRated_V
GenRated_I