Rockwell Automation 1407-CGCM Combination Generator Control Module User Manual
Page 205

Rockwell Automation Publication 1407-UM001G-EN-P - April 2013
205
Specifications Appendix D
Over-excitation Limiting - Offline
Under-excitation Limiting
Manual Excitation Control
Metering
Attribute
Range
Increment
Pickup
0…15 A DC
0.1 A DC
Time delay
0…10 s
1 s
Attribute
1407-CGCM
Real power
0…100% kW for each of 5 points
Reactive power
0…100% kvar for each of 5 points
Attribute
1407-CGCM
Range
0…15.0 A DC
Increment
0.1 A DC
Attribute
Range
Accuracy
Generator voltage
57…208V AC
0.2% (50/60 Hz)
Generator current
0…5 A AC
0.2% (50/60 Hz)
Generator frequency
10…90 Hz
±0.05 Hz
Bus voltage
57…208V AC
< 0.2% (50/60 Hz)
Bus frequency
10…90 Hz
±0.05%
Phase angle
±180°
±1.0°
Field voltage
0…200V DC
±1.25 V or ±1.0% (whichever is
greater)
Field current
0…30 A AC
±0.15 A or ±1.0% (whichever is
greater)
Power factor
-0.5…0.5
<0.4% of actual PF
Power - real and reactive
0…200% of nom
<0.4% of rated kVA
Load share
Resolution: 0.1% of full scale voltage
Load Share entity parameters
LS(+)
LS(-)
Ui = 0…5 V
Ci = 101 nF
Ii = 111 µA
Li = 0