Rotating Diode Monitor - Open and Shorted Diode Inhibit Levels

Phase Rotation Check

Soft Start Function

Voltage Matching

Over-excitation Limiting - Online

Attribute

1407-CGCM

Field current

< 1.5 A DC

Generator frequency

< 45 Hz

Generator frequency

>70 Hz

Attribute

Range

Accuracy

Pickup

67% of rated voltage

±2% of rated voltage

Time delay

1 s

±0.1 s

Attribute

1407-CGCM

Soft start initial voltage

0…90% of rated voltage in 1% increments

Soft start time

1…7200 s in 1 s increments

Attribute

1407-CGCM

Accuracy

Generator rms voltage is matched with the rms

bus voltage to within ±0.5% of the generator

voltage.

Attribute

High Limiting

Medium Limiting

Low Limiting

Pickup range

0…30.0 A DC

0…20.0 A DC

0…15 A DC

Pickup increment

0.1 A DC

0.1 A DC

0.1 A DC

Time range

0…60 s

0…120 s

Continuous

Time increment

1 s

1 s

Response time

< 3 cycles