D - specifications, Appendix d, Specifications – Rockwell Automation 1407-CGCM Combination Generator Control Module User Manual
Page 197: For i, Appendix, Control power excitation power

Rockwell Automation Publication 1407-UM001G-EN-P - April 2013
197
Appendix
D
Specifications
The CGCM unit’s electrical and physical characteristics are listed in the
following tables.
Control Power
Excitation Power
Supply
Burden
18…32V DC (24V DC nom)
(The device is to be powered by a
24V Nominal Battery or 24V DC Power Supply
with ATEX certification.)
30 W
AC ripple, max
50%, 50…120 Hz
Source
Phases
Wiring Configuration
Voltage
Frequency
VA (max)
PMG
(1)
Single-phase
PMG-A and PMG-C
Min 56 Vrms
Max 300 Vrms
Min 50 Hz
Max 342 Hz
3070
PMG
3-phase
Floating wye
Min 56Vrms L-L
Max 300 Vrms L-L
Min 50 Hz
Max 342 Hz
3070
SE
(2)
Single-phase
PMG-A and PMG-C
Min 56Vrms
Max 300 Vrms
Min 50 Hz
Max 342 Hz
3070
SE
3-phase
Floating wye
Min 56Vrms L-L
Max 300 Vrms L-L
Min 50 Hz
Max 342 Hz
3070
SE
3-phase
Grounded wye
(grounded neutral)
Min 56Vrms L-L
Max 300 Vrms L-L
Min 50 Hz
Max 342 Hz
3070
SE
3-phase
Floating delta
Min 56Vrms L-L
Max 300 Vrms L-L
Min 50 Hz
Max 342 Hz
3070
SE
3-phase
Open delta, floating
Min 56Vrms L-L
Max 300 Vrms L-L
Min 50 Hz
Max 342 Hz
3070
(1) PMG = Permanent Magnet Generator.
(2) SE = Separately Excited.