Specifications Appendix D

Bus Voltage Sensing

Auxiliary Input

Communication Ports

Phase

Wiring
Configurations

Grounded
Connection
Available

Voltage

Frequency

Single-

phase

V Bus A and

V Bus C

No

Min 57 Vrms

Max 150 Vrms

Min 20 Hz

Max 90 Hz

Three-

phase

Floating wye

No

Min 99 Vrms L-L

Max 208 Vrms L-L

Min 20 Hz

Max 90 Hz

Three-

phase

Grounded wye

(grounded neutral)

Yes

Min 99 Vrms L-L

Max 208 Vrms L-L

Min 20 Hz

Max 90 Hz

Three-

phase

Open delta, grounded

B phase

Yes

Min 99 Vrms L-L

Max 150 Vrms L-L

Min 20 Hz

Max 90 Hz

Attribute

1407-CGCM

Range

-10…10V DC

Input impedance

20 k 

Attribute

1407-CGCM

ControlNet network

ControlNet 1.5 interface

Redundancy port

DB9 Connector, 9600 bps, 8N1 (For redundant

CGCM unit use only.)

Factory port

DB15 Connector, 9600 bps, 8N1 (Not for

customer use.)