Energy Metering Considerations
Energy metering values (kW_Hrs, kVAR_Hrs, and kVA_Hrs) are provided using
a REAL data type. Values are expressed in a 32-bit floating-point format with a
precision of 7 digits. The table lists the theoretical range of a REAL value.
The energy values accumulate when the average generator line current is no less
than 1% of generator rated current. The limit that can be represented by an
energy tag is expressed by the following formulas:
When the energy tag value reaches (8,388,600 * rated kVA * % of rated load) and
the unit is still providing the same load level or less, the value will not update.
For instance, a 30 MVA machine operating at 10% load will yield an energy tag
limit of :
(8,338,600 * .1 * 30000) = 25,015,800,000 kVAh, or 2.50158 x 10
10
kVAh
When the energy tag value exceeds 8,338,600, rounding of the value begins to
occur.
The energy values are not retentive. When the 1407-CGCM unit powers up or
re-establishes a connection with the controller, the energy presets in the
Unscheduled Write table are written to the energy metering values.
Data Table
kW_Hrs Limit
8,338,600 rated kW
% of rated load
=
kVAR_Hrs Limit
8,338,600 rated kVAR
% of rated load
=
kVA_Hrs Limit
8,338,600 rated kVA
% of rated load
=
Table 12 - Unscheduled Read Data Table, Assembly Instance 5
Byte
Size in
Bytes
Type
Tag Name
Description
Units
Range
0
4
Real
AvgPF
Average Power Factor
PF
-1…1
4
4
Real
PhA_PF
Phase A Power Factor
8
4
Real
PhB_PF
Phase B Power Factor
12
4
Real
PhC_PF
Phase C Power Factor
16
4
Real
Total_kVA
Total kVA
kVA
0…3E+09
20
4
Real
PhA_kVA
Phase A kVA
24
4
Real
PhB_kVA
Phase B kVA
28
4
Real
PhC_kVA
Phase C kVA