Rockwell Automation Publication 1407-UM001G-EN-P - April 2013
167
Time Over-current Characteristic Curves Appendix A
Time Dial Setting Cross-reference
Although the time characteristic curve shapes have been optimized for each relay,
time dial settings of the CGCM unit are not identical to the settings of
electromechanical induction disk over-current relays.
The
Characteristic Curve Cross-reference
table on
page 168
helps you convert
the time dial settings of induction disk relays to the equivalent setting for the
CGCM unit.
Using Table
Cross-reference table values were obtained by inspection of published
electromechanical time current characteristic curves. The time delay for a current
of five times tap was entered into the time dial calculator function for each time
dial setting. The equivalent CGCM unit time dial setting was then entered into
the cross-reference table.
If your electromechanical relay time dial setting is between the values provided in
the table, it will be necessary to interpolate (estimate the correct intermediate
value) between the electromechanical setting and the factory setting.
Table 35 - Characteristic Curve Cross-Reference
Curve
Curve Name
Page
Similar To
1
S, Short Inverse
169
ABB CO-2
2
S2, Short Inverse
170
GE IAC-55
3
L, L1, Long Inverse
171
ABB CO-5
4
L2, Long Inverse
172
GE IAC-66
5
D, Definite Time
173
ABB CO-6
6
M, Moderately Inverse
174
ABB CO-7
7
I, I1 Inverse Time
175
ABB CO-8
8
I2 Inverse Time
176
GE IAC-51
9
V, V1 Very Inverse
177
ABB CO-9
10
V2, Very Inverse
178
GE IAC-53
11
E, E1 Extremely Inverse
179
ABB CO-11
12
E2, Extremely Inverse
180
GE IAC-77
13
A Standard Inverse
181
BS, IEC Standard Inverse
14
B, Very Inverse (It)
182
BS, IEC Very Inverse (I
2
t)
15
Extremely Inverse (I
2
t)
183
BS, IEC Extremely Inverse (I
2
t)
16
Long Time Inverse
184
BS, IEC Long Time Inverse
17
Fixed Time
N/A
N/A