Rockwell Automation Publication 1407-UM001G-EN-P - April 2013

167

Time Over-current Characteristic Curves Appendix A

Time Dial Setting Cross-reference

Although the time characteristic curve shapes have been optimized for each relay,
time dial settings of the CGCM unit are not identical to the settings of
electromechanical induction disk over-current relays.

The

Characteristic Curve Cross-reference

table on

page 168

helps you convert

the time dial settings of induction disk relays to the equivalent setting for the
CGCM unit.

Using Table

Cross-reference table values were obtained by inspection of published
electromechanical time current characteristic curves. The time delay for a current
of five times tap was entered into the time dial calculator function for each time
dial setting. The equivalent CGCM unit time dial setting was then entered into
the cross-reference table.

If your electromechanical relay time dial setting is between the values provided in
the table, it will be necessary to interpolate (estimate the correct intermediate
value) between the electromechanical setting and the factory setting.

Table 35 - Characteristic Curve Cross-Reference

Curve

Curve Name

Page

Similar To

1

S, Short Inverse

169

ABB CO-2

2

S2, Short Inverse

170

GE IAC-55

3

L, L1, Long Inverse

171

ABB CO-5

4

L2, Long Inverse

172

GE IAC-66

5

D, Definite Time

173

ABB CO-6

6

M, Moderately Inverse

174

ABB CO-7

7

I, I1 Inverse Time

175

ABB CO-8

8

I2 Inverse Time

176

GE IAC-51

9

V, V1 Very Inverse

177

ABB CO-9

10

V2, Very Inverse

178

GE IAC-53

11

E, E1 Extremely Inverse

179

ABB CO-11

12

E2, Extremely Inverse

180

GE IAC-77

13

A Standard Inverse

181

BS, IEC Standard Inverse

14

B, Very Inverse (It)

182

BS, IEC Very Inverse (I

2

t)

15

Extremely Inverse (I

2

t)

183

BS, IEC Extremely Inverse (I

2

t)

16

Long Time Inverse

184

BS, IEC Long Time Inverse

17

Fixed Time

N/A

N/A