Rockwell Automation 1407-CGCM Combination Generator Control Module User Manual
Page 86

86
Rockwell Automation Publication 1407-UM001G-EN-P - April 2013
Chapter 4
CGCM Unit Configuration
• The tags listed below determine the points shown in the UEL
configuration diagrams below. These tags are in the configuration table
and are set by the like-named fields in the UEL tab. Configure the VAR
and Watt tags with increasing real power values in point 1 through point
x.
These tags define the curve breakpoints. As shown, the curve continues
horizontally left from point 1 and vertically up from point 5. The tags are
expressed in Watts or VARs respectively.
–
Point 1 is defined by tags UEL_Curve_W_Pt1 and
UEL_Curve_VAR_Pt1
–
Point 2 is defined by tags UEL_Curve_W_Pt2 and
UEL_Curve_VAR_Pt2
–
Point 3 is defined by tags UEL_Curve_W_Pt3 and
UEL_Curve_VAR_Pt3
–
Point 4 is defined by tags UEL_Curve_W_Pt4 and
UEL_Curve_VAR_Pt4
–
Point 5 is defined by tags UEL_Curve_W_Pt5 and
UEL_Curve_VAR_Pt5
• Validate and Graph button – Updates the graph in the UEL tab after
entering new values.
Related Parameters
• UEL_En tag in the Output table
1
2
3
4
5
Real Power, Watts
Reactive Power
, V
ARs