Assembly object (class code 0x04) – Rockwell Automation 1407-CGCM Combination Generator Control Module User Manual
Page 195

Rockwell Automation Publication 1407-UM001G-EN-P - April 2013
195
Additional ControlNet Network Information Appendix C
The Get Attributes All service for instance 2 of the Identity Object returns the
following information.
Reset Service Code
The Reset service for instance 1 of the Identity Object requests that a CGCM
unit’s communication reset be performed. If excitation is enabled, the request is
denied. If excitation is not enabled, the request is accepted.
The following recognized ControlNet General Response Codes are used in
response to the reset request.
If a reset is accepted, the CGCM unit resets its communication only; the entire
CGCM unit is not reset. The CGCM unit continues to function normally
during the reset except that communication with the Logix controller is lost.
After the reset is complete, the CGCM unit automatically starts communicating
and is immediately ready for normal operation based on its previous
configuration data (for example, reconfiguration is not required).
If new configuration data is received, the CGCM unit responds as shown in the
illustrations on pages
.
Assembly Object (class code 0x04)
The Assembly Object is used to provide application specific information about a
device.
Assembly Class Instance (instance 0)
Instance 0 of any ControlNet object represents the class itself.
Table 40 - Get Attributes All (service code 0x01)
Name
Attr ID
Data Type
Value
Vendor Id
1
UINT
1 (AB)
Device Type
2
UINT
12 (Rockwell Automation Misc)
Product Code
3
UINT
113
Revision
4
USINT[2]
Major, Minor (for example 1, 5)
Status
5
WORD
Status
Serial Number
6
UDINT
Unique device serial number
Product Name
7
USINT[12]
1407-CGCM-DC
Table 41 - Reset (service code 0x05)
Response
Value
Meaning
CI_GRC_BAD_OBJ_MO DE 0x0C
A reset cannot be performed (excitation enabled)