C Universal Temperature Converter Installation Instructions
Warning
Simulation
If you have started the communication between PACTware
TM
and
Bul. 937CS-AITMP-DC1 (e. g. via
Device data
→ Establish connection), you can open the Simulation window via Device data → Simulation.
The simulation mode is started with the check box Simulation Active.
You can now specify output currents or output voltages for testing purposes. Press Enter to take over
the set numerical value.
Use the check box Simulation Active to end the simulation.
If the power supply is interrupted, the device ends the simulation.
The simulation interrupts the normal function of the device!
Before starting the simulation, make sure that no dangerous condition in the plant will
result.
You can close the simulation window with the Close button or by clicking on the
Windows-standard
⌧ button at the top right. The device will remain in simulation
mode, however, until you select Simulation Off again.
Note