C Universal Temperature Converter Installation Instructions

20

115

111

118

Connection

The slip-off terminals significantly simplify connection and
construction of switching cabinets. They allow quick and error-
free exchange of the unit when service is needed.
The terminals can be screwed on, are self-opening, and have
generous connection room for a wire diameter of up to 2.5 mm²
and coded plugs, so that leads cannot be confused.
Intrinsically safe field circuits are connected to the

blue terminals

1 to 6 of the Universal Temperature Converter. These may be
conducted using DIN EN 60079-14-compliant leads into the
hazardous area.

Non-intrinsically safe field circuits are connected to the

black

terminals 7 to 15 of the Universal Temperature Converter.
Only one sensor can be connected to the Universal
Temperature Converter.