Rockwell Automation 937CS-AITMP-DC1 Universal Temperature Converter Installation Instructions User Manual

Page 23

Advertising
background image

22

Bul. 937

C Universal Temperature Converter Installation Instructions

At this setting, the start value of the measurement range is converted to 0 mA and the end value to
20 mA. Intermediate values are converted proportionately.

Values less than the start value cannot be evaluated (output 0 mA). If the value exceeds the end value,
the output current increases linearly to a maximum of 20.5 mA (102.5 % of the measuring range).
Further increases cannot be evaluated (output 20.5 mA).

Fault current

The following table shows the values of the current output during a fault, depending on the settings.
For information on the behavior of the current output if Redundancy active has been selected, refer
to

Menu Input Extras section.

Setting

Characteristic

4 mA ... 20 mA

unlimited

Characteristics

4 mA ... 20 mA (NE 43)

4 mA ... 20 mA limited

Characteristic

0 mA ... 20 mA

Upscale

approx. 22 mA

(cannot be distinguished from

value exceeding end value)

approx. 21.5 mA

approx. 21.5 mA

Downscale

0 mA

(cannot be distinguished from

value below start value)

2.0 mA

0 mA

(cannot be distinguished

from measurement of

the start value)

Hold

last measured value before the fault

Upscale/

downscale

only makes

sense for RTD

approx. 22 mA

in the case of lead short circuit

(cannot be distinguished from

value exceeding end value)

approx. 21.5 mA

in the case of

lead short circuit

approx. 21.5 mA

in the case of lead short

circuit

0 mA

in the case of lead breakage

(cannot be distinguished from

value below start value)

2.0 mA

in the case of

lead breakage

0 mA

in the case of lead

breakage

(cannot be distinguished

from measurement of

the start value)