Bul. 937

C Universal Temperature Converter Installation Instructions

At this setting, the start value of the measurement range is converted to 4 mA and the end value to
20 mA. Intermediate values are converted proportionately.

If the value falls below the start value, the output current decreases linearly to a minimum of 3.8 mA
(-1.25 % of the measurement range). Further decreases cannot be evaluated (output 3.8 mA). If the
value exceeds the end value, the output current increases linearly to a maximum of 20.5 mA (approx.
103 % of the measurement range). Further increases cannot be evaluated (output 20.5 mA).

Setting 4 mA ... 20 mA limited

At this setting, the start value of the measurement range is converted to 4 mA and the end value to
20 mA. Intermediate values are converted proportionately.

Values below the start value cannot be evaluated (output 4 mA). Values above the end value cannot
be evaluated either (output 20 mA).

Setting 0 mA ... 20 mA

20.0

0

0

100

4.0

mA

% meas.

Start value

End value

range

20.5
20.0

0

0

100

102.5

mA

% meas.

Start value

End value

range