The following parameters can be set:

Sensor (see

Connection section):

− Resistance temperature detector: Pt10GOST etc.

− Thermocouple: TXK etc.

Potentiometer

Voltage

Connection mode (for resistance temperature detectors only, see

Connection section):

2-wire

3-wire

4-wire

Unit:
− for resistance temperature detectors and thermocouples: °F, K or °C

− for potentiometers: fixed ratio

− for voltage (sources): fixed mV
The unit selected here will be used for all respective settings and displays in PACT

ware

TM

.

Cold junction compensation (for thermocouples only):
− external (Reference temperature)

− internal (Bul 937A-TCJC)
If you have selected Ext. ref. temp., you can enter the external reference temperature
(range of values: -100 °C to 320 °C)

For an internal Cold junction compensation, you require the

Bul 937A-TCJC terminal block as

an accessory

instead of the normal terminal 1 to 3 (see Connection section).

Lead Resistance: When connecting an RTD with 2 wire connection the lead resistance of the
cabling can be entered numerically if known.

2-Wire Calibration: When connecting an RTD with 2-wire connection the lead resistance of the
cabling can be calibrated if the resistance is unknown. For calibration the sensor must be jumpered.

Sensor-breakage monitoring (for all types of sensors)

Sensor-short-circuit monitoring (for resistance temperature detectors only)

You activate or deactivate monitoring by clicking the respective checkbox
( = selected, = deselected).