C Universal Temperature Converter Installation Instructions
S
•
Undervoltage lockout: the supply voltage is too low for the outputs to work properly, the outputs
return 0 mA or 0 V, no matter which fault current/which fault voltage has been selected
•
Redundancy too large: only if Redundancy active has been selected (see
Menu Input Extra section),
if the set maximum deviation is exceeded
•
Sensor breakage: see
Menu Input section
•
Sensor short circuit: only RTD type of sensor; see
Menu Input section
•
Overrange, Underrange: measured variable outside the maximum measuring range of the selected
sensor (see
Menu Output section and Behavior of the current output or voltage output section)
•
CJC Error: if the cold junction compensation has been selected (see
Menu Input section) and a
breakage
or short circuit occurs within the Bul 937A-TCJC terminal
•
Input 1: terminals 1 to 3 (also uses terminal 4 for 4-wire resistance measurement);
Service
In menu Service the factory settings of the Bul. 937CS-AITMP-DC1 can be reloaded.
Reload the factory settings via pressing the button Factory Reset.