Chapter 5 – Programming

5-32

This group contains the necessary parameters to activate and program advanced features of the drive.

Feature

Select

[Run On Power Up]

Parameter # 14

Factory Default ‘‘Disabled”

[Run On Power Up]

Parameter Type Read & Write

This parameter enables the function that allows the drive to
automatically restart on power up regardless of what the
drive status was before power is lost. This applies only
when there is a maintained input to the start and stop
inputs. Refer to Chapter 2, Figure 2.5.

Units None

Settings ‘‘Enabled”

‘‘Disabled”

ATTENTION: This parameter may only be used as outlined in NFPA 79, paragraph 6-14 (exceptions 1-3) for
specialized applications. Equipment damage and/or personal injury may result if this parameter is used in an
inappropriate application.

[Reset/Run Tries]

Parameter # 85

Factory Default 0

[Reset/Run Tries]

Parameter Type Read & Write

Minimum 0

This value sets the maximum number of times the drive
attempts to reset a fault and restart before the drive issues
a ‘‘Max Retries Fault.” Not operative for faults 9, 10, 11,
24, 25, 26, 29, 30, 32, 33, 34, 35, 38, 39, 40, 41, 42,
43 and 48. IMPORTANT: [Reset/Run Tries] is a
cumulative count. This counter resets to zero if four (4)
minutes elapses since the last fault.

Units None

Maximum 9