FILTER
Table D.2 Filter and Metal Plate Kit Selection
Filter
Metal Plate Kit
AC Drive Type
1305-RFB-5-A
1305-MP-05-A
1305-AA02
1305-AA03
1305-MP-06-A
1305-AA04
1305-RFB-8-B
1305-MP-08-B
1305-AA08
1305-BA01
1305-BA02
1305-BA03
1305-BA04
1305-BA06
1305-RFB-12-C
1305-MP-12-C
1305-AA12
1305-BA09
RFI Filter Installation
IMPORTANT: Refer to the instructions supplied with the filter
for details.
The RFI filter must be connected between the incoming AC
supply line and the drive input terminal.
RFI Filter Leakage Current
The RFI filter may cause ground leakage currents. Therefore a
solid ground connection must be provided.
ATTENTION: To guard against possible
equipment damage, RFI filters can only be used
with AC supplies that are nominally balanced
with respect to ground. In some installations,
three-phase supplies are occasionally connected
in a 3-wire configuration with one phase
grounded (Grounded Delta). The filter must not
be used in Grounded Delta supplies, nor should
they be used in single-phase input applications.