Chapter 5 – Programming

5-8

Set Up

This group of parameters defines the basic operation of the drive and should be programmed before initial
operation. For advanced programming and information on specific parameters, refer to the flow chart on
page 5-2 & 5-3

[Input Mode]

Parameter # 21

Factory Default “Three Wire”

[Input Mode]

Parameter Type Read & Write

This parameter selects between three wire and Run
Fwd/Rev control. Refer to Chapter 2, Figure 2-5.
IMPORTANT: Power must be cycled to the drive for the
change to take effect.
IMPORTANT: See Frequency Set Group for MOP
explanation.

Units None

Setting “Three Wire”

“Run Fwd/Rev”
“3 W/2nd Acc” (2nd Accel)
“Run F/R 2nd A” (2nd Accel)
“3 Wire/MOP”
“Run F/R MOP”

IMPORTANT: This parameter cannot be
programmed while the drive is running.

[Freq Select 1]

Parameter # 5

Factory Default “Adapter 1”

[Freq Select 1]

Parameter Type Read & Write

Settings ‘‘Remote Pot”

‘‘

‘‘Preset 1”
‘‘ rese

This parameter is the factory default parameter for
selecting the frequency source that will supply the [Freq
Command]
to the drive. [Freq Select 2] or [Preset Freq
1–7]
can be selected in place of this parameter with proper
terminal block inputs. (See Chart on Page 5-31).
IMPORTANT: If an adapter that is not connected is
selected as the active frequency source, the drive will fault
on “Hz Sel Fault” (F30).

Units None

‘‘0-10 Volt”
‘‘4–20 mA”
‘‘MOP”
‘‘Adapter 1”
‘‘Adapter 2”
‘‘Adapter 3”
‘‘Adapter 4”
‘‘Adapter 5”
‘‘Adapter 6”

‘‘Preset 2”
‘‘Preset 3”
‘‘Preset 4”
‘‘Preset 5’’
‘‘Preset 6”
‘‘Preset 7”