Appendix A –
Block Diagram and Specifications
A-3
Table A.1 Specifications (cont.)
ENVIRONMENTAL SPECIFICATIONS
Enclosure
NEMA 1 (IP30) standard
Ambient Temperature
0 to 50
_C; Optional Enclosures: 0 to 40_C
Storage Temperature
-40
_C to 70_C
Relative Humidity
0 to 95% (non condensing)
Vibration
1.0 G Operational
Cooling Method
Natural Convection (no fans)
Altitude
Above 1,000 m (3,300 ft), derate at 6% of drive rated amps per 1000 m
CONTROL INPUTS
Control Input Type
Contact closure (Internal 5V supply)
DO NOT ground or apply external voltage
Start
Stop
Forward/Reverse
Configurable Inputs for 2 or 3 wire control
Jog
Momentary (non-maintained) Input
SW1
SW2
SW3
Configurable Inputs for control of 7 Preset speeds and 2 Accel/Decel times
Enable
Interlock Input to enable drive operation
External Speed
Potentiometer
10 K Ohms, 1 Watt
Analog Input
(4 to 20mA)
Input lmpedance 250 Ohms (Non-Isolated), 10 bit resolution
Analog Input
(0 to 10 V DC)
Input Impedance 100 K Ohms (Non-Isolated), 10 bit resolution