Advanced set up group (cont.), Start boost, Figure 5.10 start/run boost – Rockwell Automation 1305 AC Drive, Series A and B, Firmware 4.xx-5.xx User Manual
Page 91: Run boost

Chapter 5 – Programming
5-19
Advanced Set Up Group (cont.)
[Start Boost]
Parameter # 48
Factory Default See Table
[Start Boost]
Parameter Type Read & Write
Minimum 0 Volts
1/2
HP
3/4
HP
1
HP
2
HP
3
HP
5
HP
230V
20
Volts
25
Volts
20
Volts
22
Volts
19
Volts
N/A
This parameter sets the DC boost level for acceleration
when [DC Boost Select] is set to ‘‘Run Boost” or ‘‘Break
Point.”
Units 1 Volt
Maximum 25% of
Max. Drive
Rated
Volts
460V
31
Volts
45
Volts
40
Volts
37
Volts
33
Volts
26
Volts
Figure 5.10 Start/Run Boost
[Base Voltage]
[Base Frequency]
b
0 –
0
Voltage
Frequency
[Start Boost]
'
[Run Boost]
'
Active when [DC
Boost Select] is
set to ‘‘Run Boost”
a 150% of Start Boost
a 150% of Run Boost
[Run Boost]
Parameter # 83
Factory Default 0 Volts
[Run Boost]
Parameter Type Read & Write
Minimum 0 Volts
This parameter sets the DC boost level for constant speed
level when [DC Boost Select] is set to ‘‘Run Boost.” [Run
Boost] must be set at a value less than [Start Boost].
Units 1 Volt
Maximum 25% of Max. Drive Rated Volts