Appendix b – Rockwell Automation 1305 AC Drive, Series A and B, Firmware 4.xx-5.xx User Manual
Page 156

Appendix B –
Serial Communications
B-8
Table B.4 Parameter Grouping/User Settings (cont.)
Group
Parameter Name
Parameter #
Disolay
Units
Drive Units
Scale Factor ➁
Min
Max
Factory Setting
User’s
Setting
Freq Select 1
5
Text ➀
1
––
––
Adapter 1
Freq Select 2
6
Text ➀
1
––
–––
Remote Pot
Jog Frequency
24
Hz
100
0
400.0
10.0
Prst/2nd Accel
26
Text ➀
1
––
––
Preset
Upper Presets
72
Text ➀
1
––
––
Disabled
Accel Time 2
30
Seconds
10
0.0
3600.0
10.0
Decel Time 2
31
Seconds
10
0.0
3600.0
10.0
S
et
Preset Freq 1
27
Hz
100
0.0
400.0
0.0
y
S
Preset Freq 2
28
Hz
100
0.0
400.0
0.0
enc
Preset Freq 3
29
Hz
100
0.0
400.0
0.0
equ
e
Preset Freq 4
73
Hz
100
0.0
400.0
0.0
Freq
Preset Freq 5
74
Hz
100
0.0
400.0
0.0
F
Preset Freq 6
75
Hz
100
0.0
400.0
0.0
Preset Freq 7
76
Hz
100
0.0
400.0
0.0
Skip Freq 1
32
Hz
1
0
400
400
Skip Freq 2
33
Hz
1
0
400
400
Skip Freq 3
34
Hz
1
0
400
400
Skip Freq Band
35
Hz
1
0
15
0
MOP Increment
22
Hz/Second
1
0.00
255.00
0.00
➀ Refer to Table B.6 on pages B-13, B-14 and B-15 for the numerical equivalent of the text descriptions.
➁ Refer to page B-2.