Chapter 5 – Programming
5-5
Metering
This group of parameters consists of commonly viewed drive operating conditions such as drive output fre-
quency, output voltage, output current and command frequency. All parameters in this group are Read Only.
[Output Current]
Parameter # 54
Factory Default None
[Output Current]
Parameter Type Read Only
Minimum 0.00
This parameter displays the output current present at TB1,
terminals T1, T2 & T3 (U, V & W).
Units .01 Amps
Maximum Two Times Drive
Output Current
[Output Voltage]
Parameter # 1
Factory Default None
[Output Voltage]
Parameter Type Read Only
Minimum 0
This parameter displays the output voltage present at TB1,
terminals T1, T2 & T3 (U, V & W)
Units 1 Volt
Maximum Maximum Voltage
[Output Power]
Parameter # 23
Factory Default None
[Output Power]
Parameter Type Read Only
Minimum 0
This parameter displays the output power present at TB1,
terminals T1, T2, & T3 (U, V & W).
Units .01 kW
Maximum Two Times Rated
Drive Output Power
[DC Bus Voltage]
Parameter # 53
Factory Default None
[DC Bus Voltage]
Parameter Type Read Only
Minimum 0.00
This parameter displays the DC bus voltage level.
Units 1 Volt
Maximum 410 - 230V Drive
815 - 460V Drive