Rockwell Automation 1404-M4_M5_M6_M8 Powermonitor 3000 Installation Instructions, PRIOR to Firmware rev. 3.0 User Manual
Page 13

Publication 1404-IN007D-EN-P - October 2004
Powermonitor 3000 13
Table 10 DeviceNet Optional Communications (catalog numbers ending in -DNT)
LED
LED Color
LED State and Communications
Condition
F1
Off
Not Used
F2
Off
Not Used
NETWORK STATUS
Off
Power is off or the Powermonitor 3000 is
not online
Flashing Green
Network status is OK, no connections
established
Steady Green
Network status is OK, connections
established
Flashing Red
Recoverable communications failure; port is
restarting
Steady Red
Non-recoverable communications error;
check wiring and configuration parameters
Table 11 Ethernet Optional Communications (Series A catalog numbers ending in
-ENT)
LED
LED Color
LED State and Communications
Condition
LINK
Off
Ethernet connection is inactive
Steady Green
Ethernet connection is active
RX
Off
Ethernet is idle, no active data present on
port
Flashing Red
Active data is present on Ethernet port
TX
Off
Powermonitor 3000 is not transmitting any
data through the Ethernet port
Flashing Red
Powermonitor 3000 is transmitting data
Powermonitor 3000
F1
F2
NETWORK
STATUS
Powermonitor 3000
LINK
RX
TX