Rockwell Automation 1404-M4_M5_M6_M8 Powermonitor 3000 Installation Instructions, PRIOR to Firmware rev. 3.0 User Manual

Page 61

Advertising
background image

Publication 1404-IN007D-EN-P - October 2004

Powermonitor 3000 61

Table 47 General Specifications

Dielectric Withstand

Control Power

2000 Volts

Voltage Inputs

2000 Volts

Current Inputs

2000 Volts

Status Inputs

500 Volts

Control Relays

1600 Volts

Terminal Blocks

Power Supply and Voltage input
Terminals

12 AWG (4 mm2) max.,

9 lb-in (1.02 Nm) Torque.,

75°C or Higher Copper Wire only

Relay, KYZ outputs, Current input

terminals

(1)

14 AWG (2.5 mm2) max., 10.4 lb-in (1.18 Nm) Torque.,

75°C or Higher Copper Wire only

Status inputs, RS485

14 AWG (2.5 mm2) max.,

5 lb-in (0.56 Nm) Torque

RIO, DNT (When present)

14 AWG (2.5 mm2) max.,

5 lb-in (0.56 Nm) Torque

Operating Temperature

-20°C to +60°C (-40°F to +140°F) Cat. No. 1404-DM, 1404-Mxxxx-000, 1404-Mxxxx-DNT

+0°C to +55°C (+32°F to +131°F) 1404-Mxxxx-232, -RIO, -ENT, -CNT

Storage Temperature

-40°C to +85°C (-40°F to +185°F)

Humidity

5% to 95%, Noncondensing

Vibration

10 to 500 Hz: 2G Operational (±0.012 in.)

Shock

1/2 Sine Pulse, 11 ms duration: 30G Operational and 30G Nonoperational

(1) Recommended Ring lug: AMP part # 320634

Advertising