Table 47 General Specifications
Dielectric Withstand
Control Power
2000 Volts
Voltage Inputs
2000 Volts
Current Inputs
2000 Volts
Status Inputs
500 Volts
Control Relays
1600 Volts
Terminal Blocks
Power Supply and Voltage input
Terminals
12 AWG (4 mm2) max.,
9 lb-in (1.02 Nm) Torque.,
75°C or Higher Copper Wire only
Relay, KYZ outputs, Current input
terminals
(1)
14 AWG (2.5 mm2) max., 10.4 lb-in (1.18 Nm) Torque.,
75°C or Higher Copper Wire only
Status inputs, RS485
14 AWG (2.5 mm2) max.,
5 lb-in (0.56 Nm) Torque
RIO, DNT (When present)
14 AWG (2.5 mm2) max.,
5 lb-in (0.56 Nm) Torque
Operating Temperature
-20°C to +60°C (-40°F to +140°F) Cat. No. 1404-DM, 1404-Mxxxx-000, 1404-Mxxxx-DNT
+0°C to +55°C (+32°F to +131°F) 1404-Mxxxx-232, -RIO, -ENT, -CNT
Storage Temperature
-40°C to +85°C (-40°F to +185°F)
Humidity
5% to 95%, Noncondensing
Vibration
10 to 500 Hz: 2G Operational (±0.012 in.)
Shock
1/2 Sine Pulse, 11 ms duration: 30G Operational and 30G Nonoperational
(1) Recommended Ring lug: AMP part # 320634