Current Sense
Inputs: I1, I2, I3, I4
Overload Withstand:
15 Amps Continuous,
200 Amps for one second
Burden: 0.05 VA
Impedance: 0.002 ohms
Maximum Crest Factor at 5A is 3
Starting Current: 5 mA
Status Inputs
Contact Closure (Internal 24Vdc)
Control Relay
KYZ Output
(1) ANSI C37.90-1989 trip duty
(1) Solid State KYZ - 80mA at 240Vdc-300Vdc
Table 45 Control Relay
(1)
(1) Meets ANSI/IEEE C37.90-1989 standards for trip duty.
Rating
50/60 Hz AC rms
DC
Maximum Resistive Load
Switching
10A at 250V
(2500VA)
10A at 30V and 0.25A at
250V
Minimum Load Switching
10mA at 24V
10mA at 24V
UL 508, CSA 22.2, IEC Rating
Class
B300
Q300
Maximum Make Values
(Inductive Load)
30A at 120V
15A at 240V
(3600VA)
0.55A at 125V
0.27A at 250V
(69VA)
Maximum Break Values
(Inductive Load)
3A at 120V
1.5A at 240V
(360VA)
0.55A at 125V
0.27A at 250V
(69VA)
Maximum Motor Load
Switching
1/3 HP at 125V
1/2 HP at 250V
Table 46 Relay Life
(1)
(1) Meets ANSI/IEEE C37.90-1989 standards for trip duty.
Parameter
Number of Operations
Mechanical
5 X 10
6
Electrical
1 X 10
5
Table 44 Input and Output Ratings