Current Sense
Inputs: I1, I2, I3, I4

Overload Withstand:

15 Amps Continuous,

200 Amps for one second

Burden: 0.05 VA

Impedance: 0.002 ohms

Maximum Crest Factor at 5A is 3

Starting Current: 5 mA

Status Inputs

Contact Closure (Internal 24Vdc)

Control Relay

KYZ Output

(1) ANSI C37.90-1989 trip duty

(1) Solid State KYZ - 80mA at 240Vdc-300Vdc

Table 45 Control Relay

(1)

(1) Meets ANSI/IEEE C37.90-1989 standards for trip duty.

Rating

50/60 Hz AC rms

DC

Maximum Resistive Load
Switching

10A at 250V

(2500VA)

10A at 30V and 0.25A at
250V

Minimum Load Switching

10mA at 24V

10mA at 24V

UL 508, CSA 22.2, IEC Rating
Class

B300

Q300

Maximum Make Values
(Inductive Load)

30A at 120V

15A at 240V

(3600VA)

0.55A at 125V

0.27A at 250V

(69VA)

Maximum Break Values
(Inductive Load)

3A at 120V

1.5A at 240V

(360VA)

0.55A at 125V

0.27A at 250V

(69VA)

Maximum Motor Load
Switching

1/3 HP at 125V

1/2 HP at 250V

Table 46 Relay Life

(1)

(1) Meets ANSI/IEEE C37.90-1989 standards for trip duty.

Parameter

Number of Operations

Mechanical

5 X 10

6

Electrical

1 X 10

5

Table 44 Input and Output Ratings