MicroLogix 1500 Example Ladder Programs
The format of the command data is:
The Logic Status/Feedback read message instruction on rung 0002 is
configured as follows:
The format of the command data is:
The format of the response data is:
Data Word
Example Value
Description
N7:100
15
PowerFlex 70 node address
N7:101
16
Function Code – Write Multiple Registers
N7:102
0
Starting Register Address (40001)
N7:103
3
Number of registers to write
N7:104
18
Value for 40001 – Logic Command word
N7:105
0
Value for 40002 – not used
N7:106
8192
Value for 40003 – Reference word
Data Word
Example Value
Description
N7:110
15
PowerFlex 70 node address
N7:111
4
Function Code – Read Input Registers
N7:112
0
Starting Register Address (30001)
N7:113
3
Number of registers to read
Data Word
Example Value
Description
N7:114
3855
Value for 30001 – Logic Status word
N7:115
0
Value for 30002 – not used
N7:116
8192
Value for 30003 – Feedback word